HVI power Conductors
High-voltage-resistant, insulated down conductor for maintaining the separation distance to electrically conductive parts. Can be used for an equivalent separation distance of up to s ≤ 90 cm (in air) or s ≤ 180 cm (solid building material).
Supporting Tube with HVI power Conductor
Optically optimised installation of the HVI power Conductor inside the supporting tube creates reduced area exposed to wind.
Can be used up to an equivalent separation distance s ≤ 90 cm (in air) or s ≤ 180 cm (solid material).
The conductor length has to be stated when ordering (in steps of 0.5 m).Product detailsAir-termination Mast with HVI power Conductor
For a maximum free length of the whole air-termination system of 8.5 m.
To be fixed with three variable supports (Part No. 105 345).
Transport length 6000 mm.Product detailsHVI power Conductor
High-voltage-resistant, insulated down conductor for maintaining the separation distance from conductive parts according to IEC/EN 62305-3.
For use up to an equivalent separation distance s ≤ 90 cm (in air) or s ≤ 180 cm (solid material).Product detailsConnection Elements for HVI power Conductor / HVI power long Conductor
Product detailsSupporting Tubes for HVI power Conductor / HVI power long Conductor
Product detailsAccessories for HVI power Conductor / HVI power long Conductor
Product detailsConductor Holders for HVI power Conductor in Ex Areas
The HVI power Conductor is suitable for installation in explosion hazardous areas Ex zone 1 (gases, vapours, mists) as well as Ex zone 21 (dust). The special installation conditions safely prevent electric sparks to neighbouring metal parts when lightning current flows through the HVI power Conductor.
The HVI power Conductor has to be installed in accordance with the installation instructions.Product detailsStripping Tool for HVI power Conductors
Tool for stripping the semi-conductive sheath and the PE insulation of the HVI power Conductor (outer diameter 27 mm)- Tool consists of a of handle and various exchangeable cutting heads
- Stripping length of the HVI power Conductor is adjustable in steps of 0.2 mm (lock points) using the knob. The dial on the handle shows the length set.
Handling
Position the cutting head at the end of the conductor and turn clockwise with light pressure to cut / strip it.
The cutting head can be exchanged without tools via the bayonet coupling.Product detailsTripod for Supporting Tubes without Side Outlet
Stands for holding HVI supporting tubes for internally/externally routed HVI Conductors in/on the supporting tube, with double clamp for connection of 2x Rd 8–10 mm. Adjustable to the roof slope up to max. 10° using a variable fixing on the base holder.
The stackable concrete bases, the plastic base plates and the base holder set for holding additional concrete bases are each available separately in the accessories.Product detailsTripods for Supporting Tubes with Side Outlet
Stands for holding HVI supporting tubes for internally/externally routed HVI Conductors in/on the supporting tube, with double clamp for connection of 2x Rd 8–10 mm. Adjustable to the roof slope up to max. 10° using a variable fixing on the base holder.
The stackable concrete bases, the plastic base plates and the base holder set for holding additional concrete bases are each available separately in the accessories.Product detailsFixing Elements for Supporting Tubes
Product detailsSpacers for Omnidirectional Antennas
Product detailsConnecting components 200 kA (10/350 μs)
For use in class of LPS I and II (LPL I, II).
Clamps are tested with a 200 kA (10/350 µs) lightning impulse current, based on EN 62561-1.Product detailsCable shears for HVI Conductors
Cable shears for easily cutting the HVI light Conductor, HVI Conductor (outer diameter 20 / 23 mm), HVI power Conductor (outer diameter 27 mm) and CUI Conductor to length.
The special design of the cable shears also allows precise cutting of stranded conductors, making it easier to attach connection elements.Product details